Extech Instruments MG500 Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 15
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
MG500-EU-EN v1.0 7/13
12
TransformerTesting
Transformer tests are performed with the transformer completely disconnected from the line
andtheload.Notethatthecasegroundshouldnotberemoved.
Thefive tests listed belowwill completely test a singlephase transformer. Notethat at least 1
minuteshouldbeallowedbetweeneachtest.
1. High
voltagewindingtolowvoltage
windingandground
2. Lowvoltagewindingtohighvoltage
windingandground
3. Highvoltagewindingtolowvoltage
winding(picturedatright)
4. Highvoltagewindingtoground
5. Lowvoltagewindingtoground
NotesonMeasuringtheResistanceofaContactororCircuitbreaker
AContactororCircuitbreakermustprovidealowresistancepathtoelectricitywhenclosedbut
shouldprovideahighresistancewhenopen.Astheyage,theircharacteristicsmaydeteriorate
becauseofheavyuse,operationinadirtyenvironment,orotherfactors.
UnusualInsulationResistanceMeasurementApplications
o Specialpaintorvarnishmaybeusedasaninsulatorontransformersandotherelectrical
applications
o Insulatingblankets,suitsandglovescanalsobetested
Connect the
GREEN lead here
Connect the
RED lead here
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15

Comentarios a estos manuales

Sin comentarios