Extech Instruments 382357 Especificaciones Pagina 9

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 13
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 8
382357EUENV2.42/13
9
ServiceEntrance
Note:Multiplegroundrods,multiplegroundsi.e.groundrod(s)andwaterpipegrounds,ora
combinationmaybepresentdependingontheparticularsituation. Inthesesituationsitis
necessarytomakeyourmeasurementsbetweentheserviceentranceneutralandall
subsequentgroundpoints.
Troubleshooting
1. Snapthejawsopenandclosedtwoorthreetimesbeforeturningthemeteron
2. Donotclampontoanydeviceduringthepowerupinitializationsequence.
3. Snapthejawstwoorthreetimesafterclampingontothegroundelectrodeorrod.
4. Slightamountsofdriftmayoccurathighresistancemeasurements;thisisnormaland
shouldnotbecauseforconcern.
Blankdisplayoranyfailuremode
Replacethebatterybeforeproceeding.
StartupInitializationFailure
Thestartupcalibrationwillcontinueindefinitelyifthejawsareopenordirty.Checkthatthe
jaws’matingsurfacesareclean.Donotopenthejawswhiletheinitializationsequenceis
running.
NoiseontheGroundElectrodeorRod
Ifnoiseispresent(over3Aor30V)onthegroundelectrodeorrod,thewordNOISEwill
appearonthedisplayandreadingscannolongerbeconsideredaccurate.Beforethemetercan
beusedaccurately,thenoiseproblemmustbeaddressed.
Distribution
Panel
Ground
Rod
Water
Pipe
Vista de pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13

Comentarios a estos manuales

Sin comentarios